FAQs & Support
Hybrid Inverter
Mains Lost
Fault Reasons
- Grid power outage, AC switch or circuit is disconnected.
Troubleshooting
- Check whether the mains supply is lost.
- Check whether the AC breaker and terminal are well connected.
Grid Voltage Fault
Fault Reasons
- Grid overvoltage or undervoltage, the grid voltage is higher or lower than the set protection value.
Troubleshooting
- Check whether the impendence of the AC cable is too high to lead the grid voltage increased. Change a thicker AC cable if it is.
- Extend the voltage protection range if it is allowed by the electricity company.
Grid Frequency Fault
Fault Reasons
Grid over frequency or underfrequency, the grid frequency is higher or lower than the set protection value.
Troubleshooting
- Check whether the AC cable is correct and well connected.
- Change to another country with wider protection range if it’s allowed by the local electricity company.
DCI Fault
Fault Reasons
DC injection High. Inverter detects a higher DC component in AC output.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
ISO Over Limitation
Fault Reasons
Low system insulation resistance, which is generally caused by poor insulation to ground of the module/cable or by rainy and damp environment.
Troubleshooting
- Restart the inverter.
- Check if the insulation of the wires in PV, battery, and AC is damaged.
- Seek for help from the installer or manufacture.
GFCI Fault
Fault Reasons
Excessive leakage current.
Troubleshooting
- Restart the inverter.
- Check if the insulation of the wires in PV, battery, and AC is damaged.
- Seek for help from the installer or manufacture.
PV Over Voltage
Fault Reasons
PV over voltage is too high.
Troubleshooting
- Reduce the number of PV panels to make sure the open-circuit voltage of each string is lower than the inverter max allowed input voltage.
Bus Voltage Fault
Fault Reasons
BUS voltage is over-high.
Troubleshooting
- Check whether the input voltage is over the limitation.
- Seek for help from the installer or manufacture.
Inverter Over Temperature
Fault Reasons
Temperature anomaly, the temperature of the interior of the inverter is excessively high and out of the safe range.
Troubleshooting
- Check if the heat dissipation of the inverter is normal.
- Seek for help from the installer or manufacture.
SPI Fault
Fault Reasons
Internal communication fails. Caused by a strong external magnetic field etc.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
E2 Fault
Fault Reasons
Internal storage anomaly. Caused by a strong external magnetic field etc.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
GFCI Device Fault
Fault Reasons
GFCI device anomaly.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
AC Transducer Fault
Fault Reasons
AC transducer anomaly.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Relay Check Fail
Fault Reasons
Self-checking of relay fails. neutral & ground cable are not connected well on AC side or just occasional failure.
Troubleshooting
- Check use multi-meter if there is high voltage (normally should be lower than 10V) between N&PE cable on AC side. If the voltage higher than 10V, it means the Neutral & ground cable are not connected well on AC side or restart inverter.
- If the neutral & ground cable are connected well, please contact Sunways.
Internal Fan Fault
Fault Reasons
Internal fan anomaly
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
External Fan Fault
Fault Reasons
External fan anomaly.
Troubleshooting
Stop the inverter and disconnect the AC&DC cables.
- Check whether the fan is blocked by foreign matters. If not, replace the fan.
Bus Voltage Hard Fault
Fault Reasons
BUS voltage is over-high
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture
PV Power Low
Fault Reasons
PV power Low.
Troubleshooting
- Check if part of the PV array is sheltered.
- Check if the sunlight is sufficient at the PV installed area.
Bat OV
Fault Reasons
Battery voltage is too high.
Troubleshooting
- Check whether the battery voltage exceeds the upper limit of the battery.
- Check battery terminal wiring
Backup OV
Fault Reasons
Backup output voltage is too high.
Troubleshooting
- Restart the inverter.
- Check the inverter Backup side wiring
Bus Volt Low
Fault Reasons
Bus voltage is too low.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Hard Fault
Fault Reasons
Other faults.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Backup OP
Fault Reasons
Backup output overload.
Troubleshooting
- Reduce loads connected in the Backup side.
- Restart the inverter.
Inverter OV
Fault Reasons
Backup output overvoltage.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Inverter OF
Fault Reasons
Backup output over frequency.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Inverter OC
Fault Reasons
Backup output overcurrent.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
Phase Order Err
Fault Reasons
phase sequence error.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
SCI Fault
Fault Reasons
Internal communication fails. Caused by a strong external magnetic field etc.
Troubleshooting
- Restart the inverter.
- Seek for help from the installer or manufacture.
FLASH Fault
Fault Reasons
Internal storage anomaly. Caused by a strong external magnetic field etc.
Troubleshooting
Restart the inverter.
Seek for help from the installer or manufacture.
Meter Comm Fault
Fault Reasons
Inverter and meter communication abnormal.
Troubleshooting
- Check the Meter wiring.
- Check whether the Meter is normal.
Battery Fault
Fault Reasons
Battery fault.
Troubleshooting
1. Restart the inverter.
2. Seek for help from the installer or manufacture.
Grid-tied Inverter
ISO Over Limitation
Fault Reasons
Inverter detected that the impedance of PV+ and PV – to the ground is too low (STS < 50KΩ, STT < 100KΩ).
Probable Causes
- The validity of the grounding of the PV panel frame and bracket.
- The insulation of the PV panel itself.
- The insulation of DC cables.
- Whether the head of DC connectors is watered.
- The influence of the humidity of the weather (frost or rainy).
- The inverter self-detection problem.
Troubleshooting
- Check the grounding of the PV panel’s frame and bracket and ensure the impedance to the ground is less than 10Ω.
- Swap to insert the PV string into DC connectors one by one in turn until all PV strings have been tested in all DC connectors. If one PV string reports this fault in all DC connectors, this PV string may have the above-described problem, and vice versa.
- Use a multi-meter to measure if there is voltage between the N and PE cable.
- If the above steps have been checked and excluded, please contact the Sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
DCI Fault
Fault Reasons
The output DC component is over the selected country’s limitation.
Troubleshooting
- Turn off the DC switch and AC breaker;
- Wait about 5 mins and turn on the AC breaker and DC switch to check if this fault still exists, if it is, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Grid Frequency Fault
Fault Reasons
Inverter will show “Grid Frequency Fault” when detected the AC frequency is out of range of selected country’s limitation.
Troubleshooting
- Check if the safety country selected is comply with the installation place.
- The frequency fault is usually caused by the grid unstable. When the grid backs normal, this fault will be disappear as well.
- Check the frequency on the display to see if it is within the range of limitation. If it is, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Grid Voltage Fault
Fault Reasons
Inverter will show “Grid Voltage Fault” when detected the AC voltage is out of range of selected country’s limitation.
Troubleshooting
- Check if the impedance of the output cable is too high to lead to the grid voltage increased. Change a thicker cable to check if the problem is solved or not;
- If you are using an aluminum cable, please change to copper cable lower down the voltage;
- If this fault caused by the grid voltage in the installation place is over the limitation, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Mains Lost
Fault Reasons
Inverter will show “Mains Lost” when the AC grid disconnected.
Troubleshooting
- Check if the mains(power grid) is working normal, please enter the next step if it is;
- Check if the AC breaker or other protection switches are turned off, please enter the next step if it isn’t;
- Check the L, N and PE cables which are connected in the inverter AC terminal are in the same sequence with the marks on it;
- Use a multimeter to measure whether the voltage between L and N wire of the mains(power grid) at the inverter output terminal is around 230V, the mains is abnormal if it isn’t;
- Check if the AC breaker, knife-switch, overvoltage protector or other safety protectors are working properly;
- Please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 if all steps above have been checked and excluded.
GFCI Fault
Fault Reasons
The inverter will show “GFCI Fault” if it detects the earth leakage current exceeded the limitation.
Troubleshooting
- Insert the PV string separately in turn and if the inverter reports This error when one of the PV strings is inserted, please check if This PV string has the water seepage or broken skin problem;
- If This fault only appears in the morning or rainy day when the air humidity is very high, This fault is mostly caused by the panel aging and it will disappear when the weather is sunny;
- Please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 if all steps above have been checked and excluded.
PV Over Voltage
Fault Reasons
The inverter will show “PV Over Voltage” if it detects the PV input voltage exceeded the limitation (STS@600V, STT@1100V).
Troubleshooting
- Check the number of PV panels connected in each string and make sure the total open circuit voltage is within the limits which Sunways specified in the datasheet, if yes, please remove several pieces panel until it within the range;
- If the PV string is measured within the limits that Sunways specified, please check if it is close to the voltage on the inverter display;
- If it doesn’t match, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Bus Voltage Fault
Fault Reasons
- The voltage of PV string exceeds the inverter max allowed input voltage;
- Inverter control board is operating abnormal.
Troubleshooting
- Use a multi-meter to measure the voltage of the PV panels to see if it exceeds the inverter max allowed input voltage;
- Reduce the solar panels in each PV string moderately to make sure it’s within the inverter max allowed input voltage;
- If the measured PV string voltage is within the range but This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Inverter Over Temperature
Fault Reasons
- Inverter detected the internal temperature over the limitation.
Probable Causes:
- The inverter has been operated in environmental temperature which was over 45℃ for a long time;
- The inverter is installed in a small closed space, which is not good for heat dissipation.
Troubleshooting:
- Lower down the inverter surrounding temperature;
- Check if the installation condition is within the requests of User Manual (for instance, whether the inverter is installed in a small closed space or under the direct sunlight);
- Try to turn off the inverter for a while and wait until it cools down and tuns on it;
- If this fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
GFCI Device Fault
Fault Reasons
- There’s may unrecoverable fault that occurs.
Troubleshooting
- Turn off the AC breaker and DC switch(es);
- Wait about 5 minutes and turn on the AC breaker and DC switch(es), if This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
AC Transducer Fault
Fault Reasons
- There’s may unrecoverable fault that occurs.
Troubleshooting
- Turn off the AC breaker and DC switch(es);
- Wait about 5 minutes and turn on the AC breaker and DC switch(es), if This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Relay Check Fail
Fault Reasons
- There’s may unrecoverable fault that occurs.
Troubleshooting
- Turn off the AC breaker and DC switch(es);
- Wait about 5 minutes and turn on the AC breaker and DC switch(es), if This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
E2 Fault
Fault Reasons
- There’s may unrecoverable fault that occurs.
Troubleshooting
- Turn off the AC breaker and DC switch(es);
- Wait about 5 minutes and turn on the AC breaker and DC switch(es), if This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
SPI Fault
Fault Reasons
- There’s may unrecoverable fault that occurs.
Troubleshooting
- Turn off the AC breaker and DC switch(es);
- Wait about 5 minutes and turn on the AC breaker and DC switch(es), if This fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
No Display
Fault Reasons
- No Display
Troubleshooting
- Check whether cables are all firmly connected and DC switch is on.
- Check whether the input voltage meets the working voltage.
Sunways Battery
SOC drop off
Fault Reasons
- Voltage imbalance between battery modules
- Battery self-depletion causes SOC to be inaccurate
Troubleshooting
- Each module is fully charged to the voltage protection value
- Recharge the battery and update the latest software
If the cells of battery meet some faults,please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Over voltage
SOC light off, red light on and green light is blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
Under voltage
SOC the fourth light on, red light on and green light is blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
Over temperature
SOC the third light on, red light on and green light is blinking for 1s
Troubleshooting
Wait till the temperature of cell go back to the normal state.
Under temperature
SOC the fourth/third light on, red light on and green light is Blinking for 1s
Troubleshooting
Wait till the temperature of cell go back to the normal state.
Over curren
SOC the second light on, red light on and green light is Blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
PCB over temperature
SOC the second/fourth light on, red light on and green light is Blinking for 1s
Troubleshooting
Wait till the temperature of cell go back to the normal state.
Precharge error
SOC the second/third light on, red light on and green light is Blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
Relay error
SOC the second/third/fourth light on, red light on and green light is Blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
Self-test failure
SOC the first light on, red light on and green light is Blinking for 1s
Troubleshooting
Please contact your dealer or technical support.
Sunways Accessories
Smart Meter Shows Fault
Fault Reasons
- Wiring distance is too far
- CT direction reversed
- CT phase sequence is wrongly connected
Troubleshooting
- Check whether the distance between the meter and the inverter is too far. If it is too far, you can add a repeater to solve the problem.
- Adjust CT direction
- Adjust CT phase sequence
- If this fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
WiFi Fault
Fault Reasons
- The inverter is not turned on.
- The network is not configured.
- The network cannot connect to the Internet.
Troubleshooting
- If the Wifi stick indicator light is not on, first check whether the inverter is turned on. If not, turn on the inverter.
- The network is not connected and the inverter indicator light does not light up. Configure wifi connection hotspot through mobile phone.
- The wifi is configured with a hotspot, but still cannot access the Internet. Check whether the network is open.
Sunways Monitoring
APP Fault
Fault Reasons
- APP cannot be updated.
- The power station has no data.
Troubleshooting
- Delete the original APP and re-download and install it.
- First check whether the network is smooth. If the network is smooth, check whether the inverter is running normally.
- If this fault still exists, please contact sunways after-sales team at service@sunways-tech.com or 400 9922 958 for help.
Create end-user account
Steps to access the Sunways Monitoring System
a. Access the Sunways monitoring system by entering URL https://api.sunways-portal.com/login in the browser address box.
b. Select a proper language from the drop-down menu in the upper-right
c. Click “Click to register”. The registration page is displayed.
d. Enter the end-customer registration information as required.
e. Enter a valid email address. Click “Send”.
f. Select I have read and agree to “Privacy Policy” and “Terms of Use” and click “Owner Registration”.
g. Enter the account and password and click “Log In”
Login
Steps to Log In to the Sunways Monitoring System
a. Access the Sunways monitoring system by entering URL https://api.sunways-portal.com/login in the browser address box.
b. Select a proper language from the drop-down menu in the upper-right corner of the login page.
c. Enter the email address associated with the account in the email field.
d. Enter the password in the password field.
e. Click “Log In”.
Modify account info
Operations in the Sunways Monitoring System
a. Click the “avatar” in the upper right corner of the page and view the items in the drop down list box.
b. Click “Account Info” to change the avatar icon and username.
c. Click “Mailbox Replacement” to change the bound email.
d. Click “Change Password” to set a new password.
e. Click “Log out” to log out of Sunways monitoring system.
Plant Overview
Plant Overview Page
Click the plant name to enter the “Plant Overview” page. The power flow diagram, climate data, plant details, real-time power curve and power yield are shown here.
Device Info
Device Details Page
Click the “Device info” button at the side of “Overview” and go to the device details page to check the inverter’s basic information, real-time information, power production, and historical information.
Real-time Info
Power Generation Viewing
Select different time units at the top left of the power display section, and then select the time from the right side of the section to view the power generation corresponding to each time.
Historical Info
Operating Data Viewing
Select the different parameters to view the corresponding operating data, such as PV current, PV voltage, AC current, AC voltage, Frequency, and Temperature, then select the time from the right side of the section to view the historical curve. Hover the mouse to see the specific data.
Device Alarm
Alarm Management
Users can check relevant alarms in a timely manner and provide feedback to dealers or sunways team. We provide relevant solutions based on the alarm information. As long as the device is running normally, the alarm will disappear automatically.